GE UR6CH universal module
Technical data of product parameters
The RE.216 is equipped with either overcurrent or underimpedance starters. The setting of the parameter “StartMode” determines which of the UR6CH two is in operation.
A starter must pick up at least twice before its signal is processed (for phase selection, starting timers, signalling etc.).
Should a starter pick up only sporadically, only the backwards
measuring system and ancillary functions such as displaying
measurements etc. are enabled.
Starting signals do not reset unless all the starters have reset.The variables at the I/P’s of the overcurrent starters are the UR6CH
phase currents IR, IS and IT and the residual current IE (3I0),
respectively the neutral voltage UE (3U0). Initially, a logic determines Imax, i.e. the highest of the three phase currents IR, IS and IT.
If the value of Imax exceeds the setting of the parameter “Istart”
(overcurrent starters), each of the phase currents Iph is checked
to determine whether it exceeds the setting of the parameter
“Imin” (current enable) and also 80 % of Imax. In the case of the
residual current, the corresponding values are the setting of the
parameter “3I0min” and 25 % of Imax.
In the case of the ground current IE, it is checked whether it
exceeds the setting of the parameter “3I0min” and also 25 % of
Imax. Depending on the setting of the parameter “Earth fault
detector” (I0, I0 AND U0, I0 OR U0), it is checked at the same
time whether the residual voltage has exceeded the setting of
the parameter “3U0min” (neutral voltage enable).
The logic signals R, S, T and E are accordingly changed from
logical “0” to logical “1” or remain at logical “0”. The kind of fault
and the phases involved are thus determined, information which UR6CH
is needed forThe starting signals R, S, T and E do not reset until measurement has taken place and the impedances of all six loops lie
outside the back-up impedance zone. (If only the overcurrent
starters are in operation, there is no underimpedance starting
characteristic and relay response is determined by the setting of
the overcurrent starter “Istart”.)
Product picture display
bout us service idea
We are able to supply equipment and spare parts from different countries and manufacturers. We can solve the trouble you find in many places or worry about the quality of our products. We have great advantage on the price, E-mail the detailed information of our products. We sincerely welcome you to inquire by phone or use!
With the business philosophy of “professionalism, integrity, innovation, cooperation and win-win”, we continue to develop new products, provide high-quality services to customers, pursue customer satisfaction to the maximum extent, and continue to develop new areas of business.
Email: onewwww@foxmail.com
Introduction to main products
Focus on DCS, PLC, robot control system and large servo system.
Main products: various modules/cards, controllers, touch screens, servo drives.
Advantages: supply imported original products, professional discontinued parts, fast delivery, accurate delivery time,
Main brands include ABB Bailey, GE/FANC, FOXBORO, Invensys TRICONEX, Bentley BENTLY, A-B Rockwell, Emerson EMERSON, OVATION, MOTOROLA, XYVOM, Honeywell HONEYWELL, Rexroth, KUKA, NI, DEIF, Yokogawa, Woodward WOODWARD, Ryan, Schneider SCHNEIDER, Yaskawa, Moog MOOG, PROSOFT and other brands
reminder
For more products, please contact the email for inquiry onewwww@foxmail.com
This article from the temporal Ming sheng automation equipment co., LTD.,
link: http:www.onewwww.com
Reviews
There are no reviews yet.